5 Control inputs and outputs
5.1 Analog input EM-S1INA
5.1.1 General
The analog input of the EM-IO-02 expansion module can optionally be confi
ured as a
voltage or a current input. Parameterization of the input signal is done by the defini-
tion of a linear characteristic and assignment as a
− reference value source
(can be selected via the parameter
Reference frequency source 475),
− reference percentage source
(can be selected via the parameter
Reference percentage source 476),
− actual percentage source
(can be selected via the parameter
Actual percentage source 478, in configura-
tion x11) or
− limit value sources
(can be selected via the parameter
Limit Source 734…737).
5.1.2 Configuration voltage/current input
The analog input of the EM-IO-02 expansion module has been configured in the fac-
tory setting for a voltage signal of +/- 10 V.
Switch S3 enables the switch-over of the operation mode for an analo
current si
nal
of +/-20 mA.
S3
X410A
S2
410B
S1
ON
ON
ON
Operation mode – switch S3 Function
OFF - Voltage input OFF (to the right) –
analog input EM-S1INA is configured for a
voltage signal.
ON - Current input ON (to the left) –
analog input EM-S1INA is configured for a
current signal.
Note: With the two switches S1 and S2, the bus connection of the system bus
interface is configured (refer to chapter "System Bus Interface").